01623 650102
Facebook Twitter Linked IN

10kVA UPS - Boxer Series

  • 10kVA UPS - Boxer Series
  •  
  • Hz : 50Hz
  •  

High performance 3 phase power protection designed for maximum flexibility


  • True On Line - Double Conversion Technology (Class VFI-SS-111)
  • IGBT PWM Rectifier & Inverter Technology
  • DSP Control
  • Low Input Current THD (<3%)
  • High Input Power Factor (.0.99)
  • High Efficiency up to 93%
  • Optional Dual Input
  • Wide Input Voltage Range
  • Advanced Battery Management
  • Short Circuit and Overload Protection
  • Unlimited Number of Paralellable Modules
  • Selectable Number of Batteries
  • 500 Real Time Event Log with Detailed Parameters
  • Static & Manual Bypass Operation
  • Overload and Short Circuit Protection
  • Small Footprint and Easy Maintenance
  • Advanced Communication Capabilities
  • Perfect Generator Compatibility
  • Customisable as Frequency Converter

Technical Specifications

Model
Capacity 10kVA
Power Watt 9kW
Input
Input Voltage Range 220/380VAC -15% +18% 3P+N+PE Optional 220/380VAC -37% +22% 3P+N+PE
Input Power Factor At Full Load >0.99
Input Frequency Range 45 - 65 Hz (Selectable)
Rectifier IGBT
THDi <%3
Output
Output Voltage Range 220/380VAC, 230/400VAC and 240/415VAC 3 Phase + N ± 1%
Recovery 0% - 100% - 0% Load, Maximum Output Tolerance 5%, 1% Back to Band <40ms
Efficency Up to 93%, Eco Mode 98%
Output Frequency Range 50Hz ±0.5% Synchronous With the Network / 50Hz  ±0.01% Battery Mode
Output THD Lineer Load <%2
Non-lineer Load <%5
Crest Factor 3:1
Overload Capacity At 125% Load 10min, at 150% Load 1min
Battery
Quantity (12V DC VRLA) 2x31
Charge Value (C) Nominal 0,1 C, Adjustable
Battery Power 25% of The Device Power
Internal Battery 62 x 7Ah or 9Ah
Communication
Communication Port RS232 Standart, RS485 ve SNMP Adapter Option
Dry Contact Optional
Protocol SEC, TELNET
Standards
Quality ISO 9001 - ISO 14001 - ISO 18001
Performance EN62040 -3 (VFI-SS-111)
EMC/LVD EN62040 - 2 / EN62040 -1 EN60950
General
Running Temperature For UPS 0°C~40°C For Battery 0°C~25°C
Storage Temperature For UPS 15°C ~45°C For Batteries -10°C~60°C
Protection Class IP20
Chassis Anti-Static Paint Protection
Humidity 0-95%
Altitude <1000m, Correction Factor 1. <2000m, Correction Factor >0.92, <3000m; Correction Factor >0.84
Alerts 500  Event  Log
Paralel Operation Parallel Power Increase up to 16pcs.
EPO (Emergency Power Off) Standard
Isolation Transformer Optional
Net Weight (without battery) 100kg
Dimensions (WxDxH) 460x805x1190mm
* under certain conditions
* 3 Phase in/1 Phase Out Version is Available (10 to 30 kVA)
Makelsan reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Makelsan products previously or subsequently sold. Makelsan does not guarantee the items of the accuracy and completeness.